New SPCC template for Tier 1 facilities

EPA has published an SPCC template for facilities that qualify as Tier I. These facilities do not need to get their SPCC plans certified by a Professional Engineer.

To meet the Tier I applicability criteria, the facility must have:

  1. a total aboveground oil storage capacity of 10,000 U.S. gallons or less;
  2. no aboveground oil storage containers with a capacity greater than 5,000 U.S. gallons; and
  3. in the 3 years prior to the date the SPCC Plan is certified, had no single discharge of oil to navigable waters or adjoining shorelines exceeding 1,000 U.S. gallons, or no two discharges of oil to navigable waters or adjoining shorelines each exceeding 42 U.S. gallons within any 12-month period.*

*Please note: this does not include discharges that are the result of natural disasters, acts of war, or terrorism. When determining the applicability of this SPCC reporting requirement, the gallon amount(s) specified (either 1,000 or 42) refers to the amount of oil that actually reaches navigable waters or adjoining shorelines not the total amount of oil spilled. EPA considers the entire volume of the discharge to be oil for the purposes of these reporting requirements.